UNFIRED STEAM GENERATORS TECHNICAL
INFORMATION
STEAM
STANDARD
EQUIPMENT
STEAM
CONTROL VALVE OPTIONS
Pilot
Control Valve
A pilot operated
valve can only be used with steam as the energy source. Pilot operated
valves use steam pressure as the energy to modulate the control valve.
Steam from upstream of the valve is directed into a pilot valve. This
pilot valve has an adjustable set point and pressure sensor sensing
generated steam pressure. The pilot valve compares the set point to
the sensed pressure and regulates the amount of steam passing through
the pilot to the diaphragm in the bottom of the control valve. The
steam pressure on the diaphragm opens the valve. A pilot operated
valve has a constant bleed line leading from the diaphragm to the
downstream side of the valve. When the pilot valve senses that the
desired pressure is reached it closes; this does not allow any more
steam to pressurize the diaphragm in the bottom of the control valve.
The bleed line allows any steam pressurizing the diaphragm to be relieved
and the valve closes. In the event of high pressure or loss of building
power the limit control closes the steam line from the pilot to the
valve which closes the valve. With a supply pressure of up to 15 PSI,
3 PSI is the minimum pressure drop permitted across the valve. With
a supply pressure from 16 to 31 PSI, 10 PSI is the minimum pressure
drop permitted across the valve. With a supply pressure from 31 PSI
and above, 20 PSI is the minimum pressure drop permitted across the
valve.
Pneumatic
(Air) Control Valve
Air operated valves
are normally used in building when building control air is available.
Air operated valves use building control air pressure to modulate
the control valve. The air signal is brought to an adjustable set
point pressure sensing controller sensing generated steam pressure.
The pressure sensing controller compares the set point to the sensed
pressure. The controller regulates the amount of air that passes to
the pneumatic actuator of the valve to modulate the valve. This allows
steam to pass into the unfired steam generator coil to maintain the
set point of the controller. When the set point is achieved, no air
is passed through the pressure sensing controller and the valve is
closed. In the event of high pressure or loss of building power, the
limit control will close the air line to the valve and vent any air
to the actuator to atmosphere which closes the valve.
Electronic
Control Valve
Electronically
operated control valves use a solid state pressure sensor which is
wired to an electronic control module. The electronic module has an
adjustable set point. The control module compares the set point with
the sensed pressure and sends an electric signal to a magnetic linear
actuator on the control valve. The magnetic linear actuator modulates
the control valve and regulates the amount of steam through the valve
to maintain the set point of the controller. When the set point is
achieved, the controller sends a signal to the valve actuator and
the valve closes. In the event of high pressure or loss of building
power, the limit control closes the electric power to the controller
which closes the valve.
Steam
Traps
CEMLINE provides
float and thermostatic traps for both the drip and main trap. Float
and thermostatic traps are acknowledged as the correct traps to use
with continuously modulating control valves. Float and thermostatic
traps provide immediate drainage of condensate and include a built in
thermostatic air vent for venting air. The drain orifice is designed
to provide a water seal and eliminate the loss of any live steam under
all load conditions. Float and thermostatic traps should not be used
to lift condensate.
Inlet
Stream Strainer
Strainers are "Y"
type with blow down connection and easily removable stainless steel
strainer screen.
Source
Steam Pressure Gauge
Large,
easily readable pressure gauges to read both the source and generated
steam pressure.
Vacuum
Breaker
A vacuum
breaker will be mounted in the coil head and will break any vacuum which
might occur when the source steam is condensed.
OPTIONAL
EQUIPMENT
MAKE
UP WATER FEEDING OPTIONS
Feedwater
Pump/Condensate Receiver
As the
boiler makes steam, it is necessary to replenish the boiled off water.
This method feeds the water from a boiler feed pump unit with a condensate
tank. The condensate tank is fed with make up water and condensate.
It operates on a signal from the level controller on the Unfired Steam
Generator which starts a pump that feeds the make up water into the
Unfired Steam Generator. When the water level in the Unfired Steam Generator
is satisfied, an electrical signal from the level controller signals
the water feed pump to close. The feed water pump pressure must be 15
psi greater than the generated steam pressure. A solenoid valve and
check valve is supplied between the pump and the unfired steam generator.
Feed
Water Pump
As the
boiler makes steam, it is necessary to replenish the boiled off water.
This method uses a feed water pump which is connected to the make up
water line and is started and stopped from a signal from the level controller.
A solenoid valve and check valve is supplied between the pump and the
unfired steam generator.
AUTOMATIC
BLOW DOWN OPTIONS
Automated
Blow Down - Timer Method
Unfired Steam Generators using city water will build up an accumulation of minerals in the boiler. These minerals must be disposed by a blowdown system. The blowdown system can simply be a manual blowdown where the maintenance person would manually blow off for a set period of time for a set frequency. It is advantageous to offer an automatic blowdown system. The simplest automatic blowdown system is one that operates from timers. The CEMLINE 2001 SSCM has a built in interval and duration timer wired to a blowdown solenoid valve. The owner/operator can set an interval between blowdowns in a range from 1 to 160 hours and a blowdown duration range of 1 to 250 seconds. The automatic blowdown is a fairly simple system. The automatic timer blowdown requires the owner/operator of the Unfired Steam Generator to do some analysis to determine what duration and interval he/she wishes to have his blowdown occur. *Note: Most municipalities do not allow high temperature discharge directly into the sewer system. CEMLINE offers a type "CBO" centrifugal blow-off/condensate cooler which will receive the blow down, flash the blow down to steam, and cool the condensate going to drain.
Automated
Blow Down - Total Dissolved Solids Method
There is a more sophisticated system, which samples the boiler water and blows the boiler down when the dissolved solids exceed the set point. This is a time sample method which measures the total dissolved solids by opening the blowdown valve for an adjustable time period and measuring the blow off for dissolved solids. If the total dissolved solid exceeds the trip point, the motorized valve will remain open until the fresh water make up dilutes the boiler water to a safe level of total dissolved solids. *Note: Most municipalities do not allow high temperature discharge directly into the sewer system. CEMLINE offers a type "CBO" centrifugal blow-off/condensate cooler which will receive the blow down, flash the blow down to steam, and cool the condensate going to drain.
Automated Blow Down Location - Surface Blowdown
The unfired steam generator is a distiller creating pure water in the form of steam and leaving behind the minerals and dissolved solids in the water inside the steam generator. As more steam is produced the concentration of minerals and dissolved solids increase inside the steam generator. The concentration of dissolved solids will increase in the water until saturation point is reached. Then, the water can no longer hold all of the dissolved solids and some begin to drop out of the water in the form of suspended solids forming sludge or scale on the tube bundle and vessel. Scale formation on the tube bundle will reduce the capacity of the unfired steam generator. Higher concentrations of dissolved solids may bring about carry over of make-up water in the form of wet steam. As the total dissolved solids increase so does the surface tension of the water causing the steam bubbles to adhere to themselves making it more difficult for the steam bubbles to burst as they rise to the surface of the boiling water. Therefore, the concentration of dissolved solids tends to be increased at or near top of water level in the steam generator. Reducing the concentration of dissolved solids and suspended solids in the steam generator will provide the desired capacity and dryness of steam. A Surface Blowdown can be used to remove dissolved solids from the steam generator. Automatic blowdown controls such as a TDS control or timed blowdown can be mounted at the surface allowing the removal of dissolved solids from the water in the generator. Typically surface blowdowns are performed more frequently than bottom blowdowns.
Automated Blow Down Location - Bottom Blowdown
Higher levels of suspended solids may be found in harder make-up water conditions. Suspended Solids tend to collect in the lower part of the unfired steam generator and form scale on the tube bundle. Removal of these suspended solids can be accomplished by bottom blowdown. Automatic Bottom blowdown controls can be mounted on the bottom blowdown.
Centrifugal
Boiler Blow Off/Condensate Cooler
CEMLINE
blow down/condensate coolers are designed to receive blow down from
a steam boiler, flash the blow down to steam, and cool the condensate
going to drain.
High
Water Cut Off
In
some unusual situations, it is possible for the feedwater to fail which
could cause the Unfired Steam Generator to fill with water and flood
the entire system. To prevent this from happening, CEMLINE CORPORATION®
offers, as an option, a high water cut-off to close a feedwater ball
valve if a high water condition occurs. This option consists of a level
control connected to a high level switch. The high level switch will
send a signal to either an air operated ball valve or an electrically
operated ball valve mounted in the feedwater line. These valves are
power to open, spring to close
BOILER
WATER
STANDARD
EQUIPMENT
HTW
CONTROL VALVE OPTIONS
Pneumatic
(Air) Control Valve
Air operated
valves are normally used in building when building control air is
available. Air operated valves use building control air pressure to
modulate the control valve. The air signal is brought to an adjustable
set point pressure sensing controller sensing generated steam pressure.
The pressure sensing controller compares the set point to the sensed
pressure. The controller regulates the amount of air that passes to
the pneumatic actuator of the valve to modulate the valve. This allows
HTHW to pass into the unfired steam generator coil to maintain the
set point of the controller. When the set point is achieved, no air
is passed through the pressure sensing controller and the valve is
closed.In the event of high pressure or loss of building power, the
limit control will close the air line to the valve and vent any air
to the actuator to atmosphere which closes the valve.
Electronic
Control Valve
Electronically
operated control valves use a solid state pressure sensor which is
wired to an electronic control module. The electronic module has an
adjustable set point. The control module compares the set point with
the sensed pressure and sends an electric signal to a magnetic linear
actuator on the control valve. The magnetic linear actuator modulates
the control valve and regulates the amount of HTHW through the valve
to maintain the set point of the controller. When the set point is
achieved, the controller sends a signal to the valve actuator and
the valve closes. In the event of high pressure or loss of building
power, the limit control closes the electric power to the controller
which closes the valve.
Two
Way Valve
A two way valve
modulates from fully closed to fully open varying the amount of hot
water circulated through the coil to maintain the desired output pressure.
When closed the two way valve may cause a change in the heating water
loop pressure.
Three
Way Valve
A three way valve
modulates from directing all heating water through the coil to directing
no heating water through the coil, varying the amount of hot water
circulated through the coil to maintain the desired output pressure.
The pressure drop in the heating system will be relatively constant
with a three way valve.
HTHW
Thermometer
The dial type thermometer
will monitor HTHW temperature.
MAKE
UP WATER FEEDING OPTIONS
Feedwater
Pump/Condensate Receiver
As the
boiler makes steam, it is necessary to replenish the boiled off water.
This method feeds the water from a boiler feed pump unit with a condensate
tank. The condensate tank is fed with make up water and condensate.
It operates on a signal from the level controller on the Unfired Steam
Generator which starts a pump that feeds the make up water into the
Unfired Steam Generator. When the water level in the Unfired Steam Generator
is satisfied, an electrical signal from the level controller signals
the water feed pump to close. The feed water pump pressure must be 15
psi greater than the generated steam pressure. A solenoid valve and
check valve is supplied between the pump and the unfired steam generator.
Feed
Water Pump
As the
boiler makes steam, it is necessary to replenish the boiled off water.
This method uses a feed water pump which is connected to the make up
water line and is started and stopped from a signal from the level controller.
A solenoid valve and check valve is supplied between the pump and the
unfired steam generator.
AUTOMATIC
BLOW DOWN OPTIONS
Automated
Blow Down - Timer Method
Unfired Steam Generators using city water will build up an accumulation of minerals in the boiler. These minerals must be disposed by a blowdown system. The blowdown system can simply be a manual blowdown where the maintenance person would manually blow off for a set period of time for a set frequency. It is advantageous to offer an automatic blowdown system. The simplest automatic blowdown system is one that operates from timers. The CEMLINE 2001 SSCM has a built in interval and duration timer wired to a blowdown solenoid valve. The owner/operator can set an interval between blowdowns in a range from 1 to 160 hours and a blowdown duration range of 1 to 250 seconds. The automatic blowdown is a fairly simple system. The automatic timer blowdown requires the owner/operator of the Unfired Steam Generator to do some analysis to determine what duration and interval he/she wishes to have his blowdown occur. *Note: Most municipalities do not allow high temperature discharge directly into the sewer system. CEMLINE offers a type "CBO" centrifugal blow-off/condensate cooler which will receive the blow down, flash the blow down to steam, and cool the condensate going to drain.
Automated
Blow Down - Total Dissolved Solids Method
There is a more sophisticated system, which samples the boiler water and blows the boiler down when the dissolved solids exceed the set point. This is a time sample method which measures the total dissolved solids by opening the blowdown valve for an adjustable time period and measuring the blow off for dissolved solids. If the total dissolved solid exceeds the trip point, the motorized valve will remain open until the fresh water make up dilutes the boiler water to a safe level of total dissolved solids. *Note: Most municipalities do not allow high temperature discharge directly into the sewer system. CEMLINE offers a type "CBO" centrifugal blow-off/condensate cooler which will receive the blow down, flash the blow down to steam, and cool the condensate going to drain.
Automated Blow Down Location - Surface Blowdown
The unfired steam generator is a distiller creating pure water in the form of steam and leaving behind the minerals and dissolved solids in the water inside the steam generator. As more steam is produced the concentration of minerals and dissolved solids increase inside the steam generator. The concentration of dissolved solids will increase in the water until saturation point is reached. Then, the water can no longer hold all of the dissolved solids and some begin to drop out of the water in the form of suspended solids forming sludge or scale on the tube bundle and vessel. Scale formation on the tube bundle will reduce the capacity of the unfired steam generator. Higher concentrations of dissolved solids may bring about carry over of make-up water in the form of wet steam. As the total dissolved solids increase so does the surface tension of the water causing the steam bubbles to adhere to themselves making it more difficult for the steam bubbles to burst as they rise to the surface of the boiling water. Therefore, the concentration of dissolved solids tends to be increased at or near top of water level in the steam generator. Reducing the concentration of dissolved solids and suspended solids in the steam generator will provide the desired capacity and dryness of steam. A Surface Blowdown can be used to remove dissolved solids from the steam generator. Automatic blowdown controls such as a TDS control or timed blowdown can be mounted at the surface allowing the removal of dissolved solids from the water in the generator. Typically surface blowdowns are performed more frequently than bottom blowdowns.
Automated Blow Down Location - Bottom Blowdown
Higher levels of suspended solids may be found in harder make-up water conditions. Suspended Solids tend to collect in the lower part of the unfired steam generator and form scale on the tube bundle. Removal of these suspended solids can be accomplished by bottom blowdown. Automatic Bottom blowdown controls can be mounted on the bottom blowdown.
Centrifugal
Boiler Blow Off/Condensate Cooler
CEMLINE
blow down/condensate coolers are designed to receive blow down from
a steam boiler, flash the blow down to steam, and cool the condensate
going to drain.
High
Water Cut Off
In
some unusual situations, it is possible for the feedwater to fail which
could cause the Unfired Steam Generator to fill with water and flood
the entire system. To prevent this from happening, CEMLINE CORPORATION
offers, as an option, a high water cut-off to close a feedwater ball
valve if a high water condition occurs. This option consists of a level
control connected to a high level switch. The high level switch will
send a signal to either an air operated ball valve or an electrically
operated ball valve mounted in the feedwater line. These valves are
power to open, spring to close.
|