| Chilled Water Buffer Tanks | ||
|
|
|
The CWB solves this problem by adding volume to buffer the system. The CWB reduces the rate of change of the return water. Chillers
are designed to be useful in systems with a minimum water volume.
The minimum water volume is based upon the chiller manufacturer's
requirements, typically 3 to 6 gallons per ton when the temperature
accuracy is critical. When chiller systems are properly sized, the
chiller compressor will not short cycle. Without the proper amount
of system water, the source temperature will be reached quickly and
the compressor will shut off. Many chiller compressors can only start
3 times per hour. If the compressor is off and there is a demand for
chilled water, the demand can not be met because the compressor cannot
turn back on. This causes very unsatisfied people within the building
who cannot have the required cooling. Insufficiently sized system
problems can cause excessive compressor cycling, poor temperature
control and erratic system operations. CWB STANDARD FEATURES